Long-time pick-up adjustment type Ir (thermal protection)
|
9 regelbare Einstellungen
|
|
[Ir] long-time protection pick-up adjustment range
|
0,4 - 1 x In
|
|
Long-time protection delay adjustment type tr
|
9 regelbare Einstellungen
|
|
[tr] long-time protection delay adjustment range
|
0,7…16,6 s bei 7,2 x Ir
0,7…24 s bei 6 x Ir
12,5…600 s bei 1,5 x Ir
|
|
Thermischer Speicher
|
20 mn
|
|
Short-time protection pick-up adjustment type Isd
|
9 regelbare Einstellungen
|
|
[Isd] Short-time protection pick-up adjustment range
|
1,5 - 10 x Ir
|
|
Short-time protection delay adjustment type tsd
|
Einstellbar
|
|
[tsd] Short-time protection delay adjustment range
|
0…0,4 s I²t=aus
0,1…0,4 s I²t=ein
|
|
Instantaneous protection pick-up adjustment type Ii
|
Einstellbar 9 Parameter
|
|
[Ii] instantaneous protection pick-up adjustment range
|
2 - 15 x In
Aus
|
|
Erdschlussschutz
|
Ohne
|
|
Zonenselektive Verriegelung ZSI
|
Mit
|
|
Lokale Signalisierung
|
3 LEDs (rot) für elektrischer Fehler
1 LED (rot) für internen Fehler
|
|
Displaytyp
|
Digitale Anzeige
|
|
Messart
|
Oberwellen-Messgerät
Powermeter
|
|
Übermittlung von Daten
|
Messwert auslesen
Schutz- und Alarmeinstellungen
Wartungsanzeigen
|